Sunrise Group Co., Ltd.

home products Series of Drop-out fuse PRW15 fuse

PRW15 fuse

Product Details:

Usage High Voltage
Breaking Capacity High
Safety Standards IEC
Place of Origin Japan
Brand Name sunrise electrical appliances
Model Number PRW15

Payment & Shipping Terms:

Packaging Details: Each package contains three (one group) fuse; anti-collision panel is fit among every three fuses. Fuse in paper package

Detailed Product Description


1.       General

PRW15-12 outdoor high voltage spraying drop-out fuse provides over load and short-circuit protection to power distribution transformer and line of alternating-current 50Hz and 10kV rated voltage, the fuse with load cutoff device could be used in breaking load current of power distribution line.

2.       Application ambient conditions

a.       The altitude: ≤1000m;

b.       The ambient air temperature: -40 min, +40 max, and difference of day temperature should not more than 35;

c.       The wind speed: ≤35m/s;

d.       Dirty class: III class (porcelain support insulator), IV class (synthetic rubber support insulator);

e.       The place without pollution, exploding danger, chemistry corrosive and acute vibration.

3.       Reference standard

GB15166.3-1994  Alternating-current high voltage fuse part 3---spraying fuse

GB/T11022-1999  Common specifications for high-voltage switchgear and controlgear standards

GB/T311.1-1997  Insulation cooperation of high voltage power transmission and transformer equipments

4.       Description of type

The max breaking current (kA)

Rated current (A)

Rated voltage (kV)

Design series number

Outdoor

Fuse

Spraying

Synthetic rubber support insulator

5.       Main technical parameterssee table 1

Table 1                  Rated Parameters of Fuse

No.

Item

Unit

Parameters

1

Rated voltage

KV

12

2

Rated frequency

HZ

50

3

Rated current (the base of fuse)

A

100/200

4

Rated current of fuse-link equippedfilament

A

6200

5

Rated short-circuit breaking current (max breaking current)

KA

12.5

6

Power frequency withstand voltage (1min): wet test / dry test (between phases, phase to earth) / disconnected break

KV

34/42/48

7

Lightning impulse withstand voltage: between phases, phase to earth / disconnected break

KV

75/85

8

Mechanical life

Times

500

6.       Structure of the fusesee figure 1

The fuse is composed of support insulator, installation board (the size is shown in figure 2), active contact, upper static contact, upper connection terminal, fuse tube (fuse-carrier), bottom static contact, bottom connection terminal and so on.

Figure 1. Structure of the fuse

Bottom connection terminal

Installation

 board

Fuse tube

Bottom static contact

Support insulator

Upper connection terminal

Active contact

Upper static contact

Rated voltagekV:24;27Rated short-circuit breaking current (kA)12.5

Minimum short-circuit breaking current5A fuse

power frequency dry withstand voltagekV42  95

power frequency wet withstand voltagekV34  80

thunder impact withstand voltagekV  90  185

PRW15 fuse PRW15 fuse

Send your message to this supplier
« Prev Product 1 2 3 4 5 6 7 ... Next Product »

Other Products from this Supplier

Company Info

Sunrise Group Co., Ltd.
[China]
[Verified Member]

Business Type:Manufacturer

City: Ningbo
Province/State: Zhejiang
Country/Region : China

View Contact Details

Email this page Bookmark this page Print this Page